Wiring a 2-speed extractor fan switch: diagram, wires and location
Lucas Morel
Key takeaways
- A 2-speed VMC switch receives the live wire and sends a return for each speed to the extraction unit.
- The neutral and earth wires of a VMC go directly to the unit, bypassing the switch.
- A VMC's dedicated circuit uses 1.5 mm² wire and is protected by a 2 A breaker and a 30 mA RCD, according to Legrand.
Wiring a 2-speed VMC switch involves connecting the live wire to the L terminal and two return wires to the motor—one for low speed and the other for high speed—protected by a 2 A circuit breaker.
A mechanical ventilation system provides continuous air renewal day and night at the basic flow rate and only switches to high speed to clear steam from cooking or showering. When the wall control breaks or no longer switches, replacement may seem simple, but the cover box often conceals four wires whose colours do not indicate their function. Swapping two wires is enough to prevent the ventilation from running at low speed, even in the high-speed position. This practical guide covers the wiring steps, wiring diagram, type of control to choose, panel protection and placement, as well as the most common issue reported on forums: a system that refuses to speed up despite switching.
How to wire a VMC switch
A VMC switch operates as a two-output changeover switch: the live wire enters through the L terminal and then leaves through either the low-speed or high-speed return. Legrand describes this wiring using 1.5 mm² wires.
The mechanism fits into a standard flush-mount box: its cover can match the designer switch covers nearby if the range includes a VMC model. Aeraly products, however, require an 86 mm square box with 60 mm centres; a round box is not suitable. Stripping and tightening follow the wiring of a standard switch.
- Turn off the VMC circuit breaker, then check that there is no voltage.
- Photograph the existing installation and mark each wire with adhesive labels.
- Connect the live wire to L, then connect the return wires to the terminals marked with pictograms.
- Screw the device to the wall, restore power, and check that each speed works correctly.
2-speed VMC diagram: which wire goes to which terminal
A 2-speed VMC diagram connects three points: the electrical panel, the control and the unit. According to the Legrand guide to VMC switches, each speed is identified by the button's pictogram.
| Wire | Colour usually used | Connection |
|---|---|---|
| Live wire | Red, brown or black wire | L terminal |
| Low-speed return | Depending on the manufacturer | To the motor |
| High-speed return | Depending on the manufacturer | To the motor |
| Neutral | Blue wire | Ventilation unit terminal block |
| Earth | Green and yellow wire | Ventilation unit terminal block |
On the VMC motor side, colours vary from one brand to another. Only the terminal block label is authoritative, never the assumed colour. The neutral wire never passes through the VMC control.
Which type of switch to choose for a VMC
The type of VMC switch depends on two questions: is an off position required, and is the high speed timed? Electrical equipment manufacturers offer four families.
- No off position: one speed or the other, such as Schneider Electric's 2-speed Ovalis.
- With on, off and two speeds: the Unica 10 A.
- With a pull cord or key: the pull cord is used in the kitchen, while the key reserves the off position for the keyholder.
- Push-button: it sends a pulse to timed systems.
Aeraly's catalogue includes 12 published switches (ADAMAS, VENDÔME, CASSEL), but no 2-speed VMC model. A double switch is not a suitable replacement: its two rockers can power both speeds together.
Single, double, two-way and dimmer switches: three ranges. A ventilation switch is chosen from a manufacturer that offers one.
Discover the finishesWhich circuit breaker for a VMC
A VMC circuit breaker protects a dedicated circuit, separate from the lighting and heating. Legrand pairs it with a 30 mA AC-type RCD.
2 A, or 460 W
The Legrand guide to VMC protection generally recommends 2 A, limited to 460 W, and up to 16 A according to the manufacturer's instructions.
The manufacturer's two pages differ: one requires "a 2 A miniature circuit breaker", while the other allows more. The device's rating plate is authoritative: a single-flow VMC under 460 W remains at 2 A.
Where to place the VMC switch
The VMC switch is placed where steam is generated. The ADEME, on the choice of a ventilation system, states that a "device for switching to high flow must be accessible in the kitchen", by cord, switch or remote control.
A control in the bathroom also clears lingering condensation after a shower. It must be placed outside zones 0, 1 and 2, near the door: the protection zones around the bath set the distance.
VMC that does not switch to high speed
A VMC that does not switch to high speed often suffers from a connection fault or an unsuitable mechanism. Three checks are enough.
- Reversed returns: the ventilation runs at full speed continuously and slows down in the high-speed position.
- High-speed return poorly tightened at the terminal block: power does not reach the motor.
- Timed high speed: the Schneider Electric VMC switch FAQ mentions timers triggered by a 230 V pulse, hence the push-button.
Safety
Turn off the circuit at the panel and check that there is no voltage before carrying out any work on the box or unit. If you encounter difficulties, Legrand recommends calling an electrician.
Frequently asked questions
Which cables should be used for a VMC switch?
A VMC switch uses 1.5 mm² wires, according to Legrand: usually a red live wire, blue neutral, green and yellow earth, and two return wires in another colour. Under the ICTA conduit, mark each return at both ends before closing.
Can you turn off the VMC with the switch?
A control with an off position allows this, but the ADEME reminds us that mechanical ventilation continuously removes pollutants and moisture from the home. Switching off is reserved for maintaining the extraction vents. During normal operation, the basic flow rate is sufficient for everyday needs, with less noise at night.
Is an electrician needed to install a VMC switch?
Replacing it with an identical model, with the circuit turned off, remains within the reach of a careful homeowner. Creating a dedicated circuit at the panel or installing a dual-flow VMC requires a professional: ask an electrical contractor for a quote for an installation compliant with the NF C 15-100 standard.
Conclusion
A 2-speed VMC switch is wired with a live wire and two return wires to the motor; the neutral and earth wires go to the unit. Before carrying out the work, photograph the existing installation, mark the wires and read the rating plate: it gives the power, and therefore the protection rating, and indicates any timing that requires a push-button. Place the control in the kitchen or outside the bathroom zones. If the ventilation still refuses to speed up, call an electrical contractor.
An independent writer, he writes the technical guides for the Aeraly blog and details the electrical wiring of the home, from lighting to ventilation.